RGE13 Package Gas / Electric
seer
13
Model Number Guide
Electrical and Physical Data
R GE 13 A 36 075 L P - 1 A
Residential
Packaged
Series
A - Service Level
Revision Code
Nox (Blank Standard)
L - Low Nox
Nominal Capacity
36 - 36,000 Btuh
(24 through 60)
SEER 13
Nominal Heating
75 - 75,000 Btuh
Voltage
P - 208-230v/60hz
Single Phase
Model
Voltage/HZ/
Phase
Voltage
Range
Min.
Circuit
Amp.
Max.
Over
Current
Device
(amps)
Compressor
Condenser
Fan Motor
Indoor
Blower Motor
Exhaust
Motor
Refrig.
Charge
Weight
(lbs.)
Rated
Load
(amps)
Locked
Rotor
(amps)
Rated
Load
(amps)
Rated
HP
Nom.
RPM
Rated
Load
(amps)
Rated
HP
Rated
Load
(amps)
Rated
HP
RGE13A24050(L
208-230/60/1 197-253 15.7 20 8.3 43 1.2 1/4 1075 4.1 1/2 0.7 1/30 82
370
RGE13A24075(L) 380
RGE13A30050(L
208-230/60/1 197-253 19.3 25 11.2 54 1.2 1/4 1075 4.1 1/2 0.7 1/30 82
375
RGE13A30075(L)P 385
RGE13A36075(L)P
208-230/60/1 197-253 21.7 30 13.1 74 1.2 1/4 1075 4.1 1/2 0.7 1/30 117
405
RGE13A36100P 415
RGE13A42075(L)P
208-230/60/1 197-253 27.5 40 16.0 88 1.7 1/3 1075 5.8 3/4 0.7 1/30 102
435
RGE13A42100(L)P 445
RGE13A48100(L)P
208-230/60/1 197-253 28.4 40 16.7 84 1.7 1/3 1075 5.8 3/4 0.7 1/30 104
450
RGE13A48125P 460
RGE13A60100(L)P
208-230/60/1 197-253 38.7 60 25.0 134 1.7 1/3 1075 5.8 1 0.7 1/30 140
495
RGE13A60125P 505